|
Cooling: Perimeter Zone Vav Diffuser
Cooling
- On an increase in temperature above the cooling set point of the primary zone control thermostat, the hot supply air control damper will close (a minimum can be set for fresh air requirements).
- The cold supply air control damper will begin to open and will adjust to maintain a constant down stream static pressure. The recommended static pressure is .25"w.g. The static pressure is field adjustable.
- Cold supply air (<65 degrees F.) will flow to the Vari-Flow diffusers. A
cooling / heating change over sensor in the neck of the Vari-Flow diffusers will
change the Vari-Flow diffusers to the VAV cooling mode of operation. Upon change
over from heating to VAV cooling the individual Vari-Flow diffuser dampers will
position themselves from full open to closed as needed to reach their VAV
cooling temperature set point. A field adjustable minimum airflow / damper
position can be set. The Vari-Flow diffusers will then modulate between full
open and the minimum airflow / damper position to maintain their individual
set-point temperatures.
- The control thermostat is placed in the area of extreme for the exposure.
This is typically the area that requires heating and cooling first and is
satisfied last. The area with the zone control thermostat is called the "control
zone". The "control zone" and the diffusers that supply air to it will be
constant volume diffuser(s). As the exposure starts to approach the control
thermostat cooling set point, the cold supply air control damper will begin to
modulate the volume of cold air to maintain the set-point temperature.
NEXT: Interior Zone sequence of operation.
|